1、Microprocessor ControlledI G B T DriveInverter Motor Speed RegulatorOperating ManualN310 Serise 200V class0.42.2KW(1.24.0KVA)400V class0.7555KW(1.7110KVA)Quick Start GuideThis guide is to assist in installing and running the inverter to verify that the drive and motor are working properly. Starting,
2、 stopping and speed control will be from the keypad. If your application requires external control or special system programming, consult the N310 Instruction Manual supplied with your inverter.Step 1 Before Starting the InverterPlease review Preface and Safety Precautions (page 0-1 through 1- 3) of
3、 the N310 Instruction Manual. Verify drive was installed in accordance with the procedures as described in N310 Ambient Environment and Installation on pages 3-1 through 3-8. If you feel this was abnormal, do not start the drive until qualified personnel have corrected the situation. (Failure to do
4、so could result in serious injury.)z Check inverter and motor nameplates to determine that they have the same HP and voltage ratings. (Ensure that full load motor amps do not exceed that of the inverter.)z Remove the terminal cover to expose the motor and power terminals.a. Verify that AC power is w
5、ired to L1, L2, and L3 (pages 3-12).b. Verify that Motor leads are connected to T1, T2, and T3 (pages 3-12).(The two leads may need to be reversed if motor rotation is not correct.1. Four action of FUN, Hz/RPM, VOLT, AMP LED and display of five 7-segment displays, refer to operation description of t
6、he keypad.2. SEQ LED: 00-03(or 00-04) =1/2/3, LED Lit.3. FRQ LED: 00-05(or 00-06) = 1/2/3/4, LED Lit4. FWD LED: Forward Direction, LED action (Flash in stop, Keep Lit in operation).5. REV LED: Reverse Direction, LED action (Flash in stop, Keep Lit in operation).ivStep 2 Apply Power to the Drivez App
7、ly AC power to the Drive and observe Operator. Five 7-segment Display should read Power Voltage for 2 seconds and then read Frequency/Speed, 5.00. Five 7-segment Display and FWD LED should be flashed all the time.Step 3 Check Motor Rotations without Loadz Press RUN key (FWD LED should light); five 7
8、-segment Display should run from 0.00 to 5.00.z Check motor rotation.If it is not correct:Press STOP key. Remove AC power. Wait for LED “charge” lamp to extinguish. Reverse motor leads T1 and T2.Restart the drive and check new rotation.Step 4 Check Full Speeds at 50Hz/60Hzz Frequency/Speed can be ch
9、anged by pressing the up or down Arrow keys. To move right or left for next digit, press “” key.Press the READ / ENTER key to set the speed.z Set frequency up to 50Hz/60Hz in accordance with the last rule.z Press RUN key. Check drives acceleration to full speed.z Press STOP key to stop drive and che
10、ck deceleration.Step 5 Other OperationsRun command selection:00-03(or 00-04)Frequency command selection:00-05(or 00-06)For information, see N310 Instruction Manual.Please refer to the following pages:Set Control Mode (Vector, V/F) . p. 4-07Set Motor Rated Current . p. 4-13Set Accel .p. 4-08Set Decel
11、 .p. 4-08Set Max Speed .p. 4-08Set Min Speed .p. 4-08vQuick Start GuideThis guide is to assist in installing and running the inverter to verify that the drive and motor are working properly. Starting, stopping and speed control will be from the keypad. If your application requires external control o
12、r special system programming, consult the N310 Instruction Manual supplied with your inverter.Step 1 Before Starting the InverterPlease review Preface and Safety Precautions (page 0-1 through 1- 3) of the N310 Instruction Manual. Verify drive was installed in accordance with the procedures as descri
13、bed in N310 Ambient Environment and Installation on pages 3-1 through 3-8. If you feel this was abnormal, do not start the drive until qualified personnel have corrected the situation. (Failure to do so could result in serious injury.)z Check inverter and motor nameplates to determine that they have
14、 the same HP and voltage ratings. (Ensure that full load motor amps do not exceed that of the inverter.)z Remove the terminal cover to expose the motor and power terminals.a. Verify that AC power is wired to L1, L2, and L3 (pages 3-12).b. Verify that Motor leads are connected to T1, T2, and T3 (page
15、s 3-12).(The two leads may need to be reversed if motor rotation is not correct.1. Four action of FUN, Hz/RPM, VOLT, AMP LED and display of five 7-segment displays, refer to operation description of the keypad.2. SEQ LED: 00-03(or 00-04) =1/2/3, LED Lit.3. FRQ LED: 00-05(or 00-06) = 1/2/3/4, LED Lit
16、4. FWD LED: Forward Direction, LED action (Flash in stop, Keep Lit in operation).5. REV LED: Reverse Direction, LED action (Flash in stop, Keep Lit in operation).ivStep 2 Apply Power to the Drivez Apply AC power to the Drive and observe Operator. Five 7-segment Display should read Power Voltage for
17、2 seconds and then read Frequency/Speed, 5.00. Five 7-segment Display and FWD LED should be flashed all the time.Step 3 Check Motor Rotations without Loadz Press RUN key (FWD LED should light); five 7-segment Display should run from 0.00 to 5.00.z Check motor rotation.If it is not correct:Press STOP
18、 key. Remove AC power. Wait for LED “charge” lamp to extinguish. Reverse motor leads T1 and T2.Restart the drive and check new rotation.Step 4 Check Full Speeds at 50Hz/60Hzz Frequency/Speed can be changed by pressing the up or down Arrow keys. To move right or left for next digit, press “” key.Pres
19、s the READ / ENTER key to set the speed.z Set frequency up to 50Hz/60Hz in accordance with the last rule.z Press RUN key. Check drives acceleration to full speed.z Press STOP key to stop drive and check deceleration.Step 5 Other OperationsRun command selection:00-03(or 00-04)Frequency command select
20、ion:00-05(or 00-06)For information, see N310 Instruction Manual.Please refer to the following pages:Set Control Mode (Vector, V/F) . p. 4-07Set Motor Rated Current . p. 4-13Set Accel .p. 4-08Set Decel .p. 4-08Set Max Speed .p. 4-08Set Min Speed .p. 4-08vPrefaceChapter 0Preface0.1 PrefaceTo extend th
21、e performance of the product and ensure personnel safety, please read this manual thoroughly before using the inverter. Should there be any problem in using the product that cannot be solved with the information provided in the manual, contact your nearest TECOs technical or sales representative who
22、 will be willing to help you.PrecautionsThe inverter is an electrical product. For your safety, there are symbols such as “Danger”, “Caution” in this manual as a reminder to pay attention to safety instructions on handling, installing, operating, and checking the inverter. Be sure to follow the inst
23、ructions for highest safety.DangerCautionIndicates a potential hazard that could cause death or serious personal injury if misused.Indicates that the inverter or the mechanical system might be damaged if misused. Dangerz Do not touch any circuit boards or components after the power is turned off and
24、 while the charging indicator is still lit. (The light will fade)z Do not make any connections when the inverter is powered on. Do not check parts and signals on circuit boards during the inverter operation.z Do not disassemble the inverter or modify any internal wires, circuits, or parts.z Ground t
25、he ground terminal of the inverter properly.For 200V class ground resistance 100 or below. For 400V class 10 or below.Make sure that grounding conductors are adequately sized and are according to your local safety regulations. Cautionz Do not perform a voltage test on parts inside the inverter. High
26、 voltage can destroy the semiconductor components.z Do not connect T1, T2, and T3 terminals of the inverter to any AC input power supply.z CMOS ICs on the inverters main board are susceptible to static electricity. Do not touch the main circuit board0.2 Product InspectionTaian inverters have all pas
27、sed the function test before delivery. Please check the following when you receive and unpack the inverter:z The model of the inverter are the same as those specified in your purchase order.z Check for any damages caused by transportation. Please do not apply power, and contact a TECO sales represen
28、tative if any of the above problems occurred.0-1Chapter 1 Safety PrecautionsChapter 1Safety Precautions1.1 Operation Precautions1.1.1. Before Power Up CautionThe line voltage applied must comply with the inverters specified input voltage.(See product nameplate) DangerMake sure the main circuit conne
29、ctions are correct. L1 , L2 and L3 are power-input terminals and must not be mistaken for T1, T2 and T3. Otherwise, inverter damage can result. Cautionz To avoid the front cover from disengaging or other damage, do not carry the inverter by its cover. Support the drive by its heat sink when transpor
30、ting. Improper handling can damage the inverter or injure personnel, and should be avoided.z To avoid the risk of fire, do not install the inverter on flammable objects. Install on nonflammable objects such as metal surfaces.z If several inverters are placed in the same control panel, provide heat e
31、xtraction means to keep the temperature below 40 to avoid overheat or fire hazard.z When removing or installing the operator keypad, turn OFF the power first, and secure the keypad correctly to avoid keypad operation or display failure.WarningThis product is sold subject to IEC 61800-3. In a domesti
32、c environment this product may cause radio interference in which case the user may be required to apply corrective measures.Note: Do not install a drive equipped with EMC filter on IT (unearthed) systems. EMC filter capacitors connect the supply network to earth potential which May cause a danger or
33、 damage the unit.1-1Chapter 1 Safety Precautions1.1.2. During Power Up Dangerz Do not insert or remove input connections to the inverter when powered up to avoid damage to the control board resulting from possible voltage surge due to contact bounce.z When the momentary power loss is short, the inve
34、rter still has enough storage power to control the circuit. Therefore, when power is re-applied, the inverter will automatically restart depending on the setup of 04-03/04-04.z When momentary power loss is longer than 2 seconds (the larger of horse power, the longer of time), the inverter does not h
35、ave enough storage power to control the circuit; Therefore, when the power is re-applied, the operation of the inverter is based on the setup of 00-03(or00-04) /04-09 and the condition of external switch, this is considered to berestartin the following paragraphs.z When restarting the inverter, the
36、operation of the inverter is based on the setup of 00-03(or00-04) and 04-09 and the condition of external switch (FWD/REV button). Attention: the start operation will be regardless of 04-03/04-04/04-06/04-07.1. When 00-03(or00-04) =0, the inverter will not automatically run after restart.2. When 00-
37、03(or00-04) =1 and the external switch (FWD/REV button) is OFF,the inverter will not run after restart.3. When 00-03(or00-04) =1, the external switch (FWD/REV button) is ON, and 04-09=0, the inverter will run automatically after restart.Attention: To ensure safety, please turn off the external switc
38、h (FWD/REV button) after power loss, to protect machines from possible damage and potential injury to personnel on sudden resumption of power.z If 4-09 is set to 0 (direct start up), please refer to the description and warnings for 04-09 to verify the safety of operator and machine.1.1.3. Before Ope
39、ration DangerMake sure the model and inverter capacity are the same as that set in parameter 12-00. CautionOn power up the supply voltage set in parameter 05-03 will flash on display for 2 seconds.1-2Chapter 1 Safety Precautions1.1.4. During Operation DangerDo not connect or disconnect the motor dur
40、ing operation. Otherwise, the over-current will cause the inverter to trip or damage the unit. Dangerz To avoid electric shock, do not take the front cover off when power is on.z The motor will restart automatically after stop when auto-restart function is on. In this case, use caution while working
41、 near the drive, motor, or driven equipment.z Note: The stop push button and external stop command have no safety function.For Emergency stop, it is necessary to use a correct latch type push button and an appropriate circuit or devices to ensure safety. Cautionz Do not touch heat-generating compone
42、nts such as heat sinks and braking resistors.z The inverter can drive the motor from low speed to high speed. Verify the allowable speed range of the motor and the load before operation.z Note the settings related to the braking unit.z Do not check signals on circuit boards while the inverter is run
43、ning. CautionAllow 5 minutes after disconnecting power before disassembling or checking the components. The power led should not be illuminated.1.1.5. During Maintenance CautionThe Inverter can be used in environment in temperature range from14-104 (-10-40) and relative humidity of 95%.Inverter Disp
44、osal Cautionz Please dispose of this unit with care as an industrial waste and according to your required local regulations.z The capacitors of inverter main circuit and printed circuit board are considered as hazardous waste and must not be burnt.z The Plastic enclosure and parts of the inverter such as the top cover board will release harmful gases if burnt.1-3Chapter 2 Description of modelsChapter 2Definition of model
侵权处理QQ:3464097650--上传资料QQ:3464097650
【声明】本站为“文档C2C交易模式”,即用户上传的文档直接卖给(下载)用户,本站只是网络空间服务平台,本站所有原创文档下载所得归上传人所有,如您发现上传作品侵犯了您的版权,请立刻联系我们并提供证据,我们将在3个工作日内予以改正。