1、本工程用电负荷计算表建设单位:项目名称:设 计 人:日期:序变、配电所消防装设需要功率计算功率回路电流开关负荷备注编号及用电功率功率系数因数有功功率无功功率视在功率电流倍数整定等级号设备组名称(kW)(kW)(Kx)(cos)(kW)(kVar)(kVA)(A)(1.15)(A)2号变压器照明W103G一层温泉大厅1000.800.9080.0038.7588.89134.680.00W105G三层商业60600.800.8048.0036.0060.0090.910.00W106G三层商业80800.800.8064.0048.0080.00121.210.00W107G四层办公,六层机械设
2、备300.800.8024.0018.0030.0045.450.00W110G二层后勤办公1000.800.8080.0060.00100.00151.520.00W127Gb应急照明13130.800.8010.407.8013.0019.700.00W128Gb应急照明21210.800.8016.8012.6021.0031.820.00W102G景观照明1000.800.8080.0060.00100.00151.520.00W101G设备房15150.800.8012.009.0015.0022.730.00W102P新风机107.90.800.8086.3264.74107.90
3、204.360.00W1011#照明总箱1551550.800.80124.0093.00155.00234.850.00W1022#照明总箱1151150.800.8092.0069.00115.00174.240.00W1033#照明总箱1801800.800.80144.00108.00180.00272.730.00W1044#照明总箱1001000.800.8080.0060.00100.00151.520.00W107P新风机62.30.800.8049.8437.3862.30117.990.00W108P地下室排风13.90.800.8011.128.3413.9026.330
4、.00W106P桑拿浴1200.800.8096.0072.00120.00181.820.00W124Pb洗衣房50500.800.8040.0030.0050.0075.760.00变变压压器器计计算算W*照照明明小小计计1895190.700.80363.30272.48454.13688.07W*冷冷机机小小计计0107.90.750.8080.9360.69101.16153.27W*汤汤池池照照明明小小计计5505500.550.80302.50226.88378.13572.92WS桑桑拿拿干干线线小小计计50246.20.700.80172.34129.26215.43326.
5、40变变压压器器合合计计7891423.10.650.80919.07689.301148.83Kp=0.9;Kq=0.95789.01423.10.610.79873.11675.511103.92无无功功补补偿偿容容量量-360补补偿偿后后合合计计789.01423.10.610.94873.11315.51928.37变变压压器器装装设设容容量量1250变变压压器器负负荷荷率率74.27%变变压压器器损损耗耗:Kpb=0.019.28Kqb=0.0546.42高高压压侧侧负负荷荷1423.10.620.93882.40361.93953.743号变压器w101k制冷机2200.900.8
6、0198.00148.50247.50416.671.20500w102k制冷机2200.900.80198.00148.50247.50416.671.20500w103k制冷机2200.900.80198.00148.50247.50416.671.20500w109k冷却塔22.50.900.8020.2515.1925.3142.611.4863W107K锅炉48.60.800.8038.8829.1648.6092.052.17200w104K新风机900.800.8072.0054.0090.00170.451.17200w105K新风机1110.800.8088.8066.601
7、11.00210.231.19250变变压压器器合合计计0932.10.870.80813.93610.451017.41Kp=0.95;Kq=0.980.0932.10.830.79773.23598.24977.64无无功功补补偿偿容容量量-300补补偿偿后后合合计计0.0932.10.830.93773.23298.24828.76变变压压器器装装设设容容量量1000变变压压器器负负荷荷率率82.88%变变压压器器损损耗耗:Kpb=0.018.29Kqb=0.0541.44高高压压侧侧负负荷荷932.10.840.92781.52339.68852.154号变压器W101S水处理设备13
8、1310.400.8052.4039.3065.50198.481.26250W102S水处理设备461090.400.8043.6032.7054.50165.151.21200W103S水处理设备7620.400.8024.8018.6031.00117.422.13250W104S中央处理机房500.400.8020.0015.0025.0094.701.32125W106S室内泳池大厅11500.400.8060.0045.0075.00213.071.17250W107S室内泳池大厅21500.400.8060.0045.0075.00213.071.17250W108S室内泳池大厅
9、31620.850.85137.7085.34162.00245.451.28315W109S室内泳池大厅41620.850.85137.7085.34162.00245.451.28315W109S室内泳池大厅51620.850.85137.7085.34162.00245.451.28315第 1 页,共 4 页W110S室内泳池大厅61620.850.85137.7085.34162.00245.451.28315W107S山景全势泳池11500.400.8060.0045.0075.00213.071.17250W108S山景全势泳池21000.400.8040.0030.0050.0
10、0151.521.19180W109S湖水泳池11500.400.8060.0045.0075.00213.071.17250W110S湖水泳池21000.400.8040.0030.0050.00151.521.19180变变压压器器合合计计018000.560.831011.60686.961222.80Kp=0.95;Kq=0.980.01800.00.530.82961.02673.221173.36无无功功补补偿偿容容量量-360补补偿偿后后合合计计0.01800.00.530.95961.02313.221010.77变变压压器器装装设设容容量量1250变变压压器器负负荷荷率率80
11、.86%变变压压器器损损耗耗:Kpb=0.0110.11Kqb=0.0550.54高高压压侧侧负负荷荷1800.00.540.94971.13363.751037.021号变压器W101Pa变电所动力20200.800.8016.0012.0020.0034.090.00W103Pa消防泵13400.000.850.000.000.00238.860.00W102Pa消防控制室15150.800.8012.009.0015.0028.410.00W104Pa排烟风机35.700.000.800.000.000.0067.610.00W105Pa排烟风机5100.000.800.000.000.
12、0096.590.00W112Pa排水泵7.37.30.800.805.844.387.3013.830.00W111Pa生活水泵13.513.51.000.8013.5010.1316.8825.570.00W119Pa6层厨房、卫星30300.900.8027.0020.2533.7556.820.00W115Pa制冷库50500.500.8025.0018.7531.2594.700.00W118Pa电梯16160.350.505.609.7011.2048.480.00W130Pa电梯880.350.502.804.855.6024.240.00W120Pa电梯24240.350.50
13、8.4014.5516.8072.730.00W106Pa消防电梯16160.350.505.609.7011.2048.480.00W126Pa取款机330.800.802.401.803.005.680.00W125Pa演艺中心65650.800.8052.0039.0065.00123.110.00W114Pa后勤、设备监控中心 60600.800.8048.0036.0060.00113.640.00W101Ga通道,SPA,桑拿80800.600.9048.0023.2553.33134.680.00W102Ga卡拉ok20200.800.9016.007.7517.7833.670
14、.00W103Ga演艺中心20200.800.9016.007.7517.7833.670.00W112Ga设备监控中心20200.800.9016.007.7517.7833.670.00W111Ga健身房、通道20200.500.9010.004.8411.1133.670.00W104Ga三层全部50500.500.9025.0012.1127.7884.180.00w128pa二层厨房30300.500.6615.0017.0722.7368.870.00w129pa三层餐厅10100.500.665.005.697.5822.960.00W121Pa四层厨房1201200.350.6
15、642.0047.8163.64220.390.00W122Pa五层厨房1201200.350.6642.0047.8163.64220.390.00W107Ga五层会议15150.800.9012.005.8113.3325.250.00W106Ga四层餐厅60600.800.9048.0023.2553.33101.010.00W108Ga五层宴会厅50500.800.9040.0019.3744.4484.180.00W109Ga六层餐厅,厨房80800.350.6628.0031.8742.42183.650.00W1071#空调总箱850.750.8063.7547.8179.691
16、44.890.00W1082#空调总箱760.750.8057.0042.7571.25129.550.00W1093#空调总箱120.50.750.8090.3867.78112.97205.40W1104#空调总箱1260.750.8094.5070.88118.13214.77变变压压器器合合计计1243.51430.30.620.79892.77681.451123.12Kp=0.95;Kq=0.981243.51430.30.590.79848.13667.821079.49无无功功补补偿偿容容量量-360补补偿偿后后合合计计1243.51430.30.590.94848.13307
17、.82902.26变变压压器器装装设设容容量量1250变变压压器器负负荷荷率率72.18%变变压压器器损损耗耗:Kpb=0.019.02Kqb=0.0545.11高高压压侧侧负负荷荷1430.30.600.92857.15352.94926.97变压器总装机容量(补偿后)合计10KV侧5585.500.630.933492.191418.303769.22Kp=0.9;Kq=0.955585.500.560.923142.971347.383419.61选选变变压压器器台台数数:变变压压器器总总装装设设容容量量4750175.93无无功功总总补补偿偿容容量量-138027000.0序变、配电所
18、消防装设需要功率计算功率回路电流开关负荷备注编号及用电功率功率系数因数有功功率无功功率视在功率电流倍数整定等级号设备组名称(kW)(kW)(Kx)(cos)(kW)(kVar)(kVA)(A)(1.15)(A)第 2 页,共 4 页 应急负荷计算项目名称:保障日日期期:计算人:设设备备功功率率需需要要系系数数功功率率因因数数 计计算算负负荷荷负负 荷荷 名名 称称 有有功功功功率率无无功功功功率率视视在在功功率率(KW)KxCOSf f(KW)(KVar)(KVA)变电所动力200.800.8016.0012.0020.00消防泵00.000.850.000.000.00消防控制室150.80
19、0.8012.009.0015.00排烟风机00.000.800.000.000.00排烟风机00.000.800.000.000.00排水泵5.10.800.804.083.065.10生活水泵13.50.800.8010.808.1013.506层厨房、卫星300.800.8024.0018.0030.00制冷库500.500.8025.0018.7531.25电梯160.350.505.609.7011.20电梯80.350.502.804.855.60电梯350.350.5012.2521.2224.50消防电梯160.350.505.609.7011.20取款机30.800.802.
20、401.803.00演艺中心650.800.8052.0039.0065.00后勤、设备监控中心600.800.8048.0036.0060.00制冷机00.800.850.000.000.00制冷机00.800.850.000.000.00新风机00.800.800.000.000.00桑拿浴00.500.800.000.000.00地下室排风00.800.800.000.000.00员工厨房动力00.350.600.000.000.00应急照明130.900.9011.705.6713.00应急照明210.900.9018.909.1521.00通道,SPA,桑拿800.600.9048.
21、0023.2553.33卡拉ok200.800.9016.007.7517.78演艺中心200.800.9016.007.7517.78设备监控中心200.800.9016.007.7517.78健身房、通道200.500.9010.004.8411.11三层全部500.500.9025.0012.1127.78二层厨房300.500.9015.007.2616.67三层餐厅100.500.905.002.425.56四层厨房1200.350.6642.0047.8163.64五层厨房1200.350.9042.0020.3446.67五层会议150.800.9012.005.8113.33四
22、层餐厅600.800.9048.0023.2553.33五层宴会厅500.800.9040.0019.3744.44六层餐厅,厨房800.350.9028.0013.5631.11洗衣房500.600.8030.0022.5037.50设备房150.800.8012.009.0015.00商业600.800.8048.0036.0060.00设备房800.800.8064.0048.0080.001#总箱1550.550.8085.2563.94106.562#总箱1150.550.8063.2547.4479.063#总箱1800.550.8099.0074.25123.754#总箱1000.550.8055.0041.2568.75小小计计1820.60.590.821070.63751.651308.14发发电电机机装装设设容容量量 CAPACITYCAPACITYOFOF GENERATORGENERATOR1200 发发电电机机负负荷荷率率 LOADLOADRATERATE OFOF GENERATORGENERATOR89.22%