1、变压器常见故障现场分析与处理分析日期(ul/l)氢COCO2CH4C2H6C2H4C2H2总烃90.6.820.16502655.70.914.6022.2290.6.1422.467.243470.511.1018.690.6.1923.766.93125.70.210.7016.590.6.2318.6120.7507.44.80.59.10.214.6分 析 日期(ul/l)氢COCO2CH4C2H6C2H4C2H2总烃91.11.414.86341103311.131.0.60.112.992.4.440.8675176914.71.98.86.932.292.4.546.994120
2、1818.42.811.28.540.992.4.1033.3896203411.31.711.66.030.592.42844948326217.72.29.36.635.8分 析 日期(ul/l)氢COCO2CH4C2H6C2H4C2H2总烃 90.10.12 16.8525388549.416.5283.0.214990.11.1034.9640469098.933152.20.1284.291.1.2437.86554638155.353.62200.2427.391.7.16417466246285.9122.54560.2864.491.12.7745136538.859.3.49
3、.70.314891.12.202441.413915032.41350.228291.12.28060131757.733.21350.2218.492.1.3072174357.736.1146.40252.6表1 SFSZ740000/110变压器绕组直流电阻测量数据天气:晴,气温80C 高压绕组直流电阻(运行分头)A 504.3 m B 507.7 mC 503.7m中压绕组直流电阻AmOm 60.81 mBmOm 60.78 mCmOm 61.70 m低压绕组直流电阻ab 7.296m bc 8.217m ca 7.325 m 低压绕组直流电阻(折算值)a 10.549 m b 10
4、.475 m c 13.488 m 表2 SFSZ740000/110变压器油色谱分析检测值 单位:ul/l 气体组分 分析时间 H2COCO2CH4C2H4C2H6C2H2总烃2002.10.16 (故障前)251019574224.91 03.65028.562002.10.22(17:00)671118586835.2810.53.9550.9100.642002.10.22(21:00)7313066720344.34.73981.63气体组分分析日期H2COCO2CH4C2H4C2H6C2H2总烃07.12 故障前3399820793.374.471.861.2810.9808.23
5、上午故障后58129832955.496.252.430.79.14.9108.23下午故障后55121530785.316.492.120.9414.86表3:SFSZ7220/150000变压器油色谱检测值 单位:ul/l 基于差动故障点明显(且不在变压器内部),色谱分析和电气试验无异常,随对变压器差动保护回路通电检查后,确定对变压器于8月24日冲击送电。结果变压器重瓦斯保护动作,检查瓦斯继电器内存有大量气体,点火能够燃烧;取油样色谱分析结果如表4:表4:SFSZ7220变压器冲击送电后油色谱检测值 单位:ul/l气体组分分析日期H2COCO2CH4C2H4C2H6C2H2总烃08.25
6、5121317295887163.611.5185.2447.3表5:SFSZ7220/150000变压器低压绕组直流电阻测量数据 单位:abbcacabc0.036740.032080.032020.051640.068330.05147由于b相电阻明显增大,说明35KV低压线圈b相存在匝间短路并有断匝现象。8月28日变压器吊罩检查,各部位紧固件无明显松动,外侧能见高压线圈无变形,外观可视油道无堵塞,低压线圈变形情况无法检查,发现中相低压线包内侧与铁芯立柱之间有烧损的纸绝缘灰烬和少量铜熔渣;变压器扣罩密封,充干燥的氮气存放。从以上检查试验和色谱分析结果推断,变压器低压线圈b相匝间短路并有断匝
7、是变压器重瓦斯动作的直接原因。试验日期氢气一 氧 化碳二 氧 化碳甲烷乙烯乙烷乙炔总烃备注05.06.29(故障前)511354120.680.821.1202.63油样05.12.28(故障前)662053990.830.580.6202.03油样06.01.18(故障后)2943511161002287696686851298026209气样06.01.18(故障后)822133651.656.030.488.2716.43油样 相别分接位置RAORBORCO三相不平衡系数%相别分接位置RAORBORCO三相不平衡系数%10.36810.3690.473926.2100.32370.323
8、00.427829.220.36110.36220.466926.7110.33020.32970.434628.730.35380.35490.459727120.33710.33690.441628.140.34680.34790.452627.7130.34390.34380.448727.650.33990.34060.445528.1140.35020.35020.455027.260.33350.33450.439328.6150.35640.35650.461426.870.32740.32820.433029.1160.36270.36300.467626.380.32120.
9、32210.426729.5170.36920.36930.474125.990.31370.31440.418630 低压侧Rab=0.004131 Rbc=0.004133 Rca=0.004146 线间不平衡系数0.3%表1 变压器油色谱检测值 单位:ul/l 成份 分析日期 H2 COCO2CH4 C2H6C2H4C2H2总烃99年8月(事故前)14958579316.464.9413.20.1834.7899年11月(事故后)2351287579939.459.6353.2753.89156.243、切换开关油箱密封不良 3、1 某主变(SFSZ740000/110),所用有载开关为
10、ZYI系列国产开关,90年5月18日安装投运,由于供电用户对电压合格率要求高,调压频率比较频繁,当月对变压器油色谱分析异常,色谱分析数据如表2。表2 变压器油色谱检测值 单位:ul/l 成份分析日期 H2 CO CO2 CH4 C2H4 C2H6 C2H2 总烃95.5.181236537560.671.08001.7595.5.206758743888.765.796.276.8727.6995.5.2376635427612.66.16.348.9332.63油中微水含量为:11.5uL/L。由于气体组分中C2H2占主要成份,且超出注意值,色谱分析三比值法判断,初步怀疑变压器内部存在高能量的放电故障。表1:特征气体与故障性质的关系序号故障性质特征气体的特点1一般过热性故障总烃较高,C2H2小于5ul/l的注意值,故障处于早期阶段,产气的速率较慢2严重过热性故障总烃高,C2H2可能大于5ul/l,但尚未构成总烃的主要成分,H2的含量较高,产气速率快。3局部放电总烃不高,H2的含量大于150 ul/l的注意值,CH4占总烃的主要成分4火花放电总烃不高,C2H2含量较高,往往大于10ul/l,H2的含量较高。5电弧放电总烃高,C2H2含量高往往构成总烃的主要成分,H2的含量高。